- INPUT
- Open collector : 12VDC/4mA
- Voltage pulse : Square or sine waveforms
- Dry contact : 12VDC/4mA
- Current pulse input impedance : 250¥Ø
- Input cut off bias voltage adjustment : 0~6VDC max
- Minimun stabile frequency : 50Hz
- INSTALLATION
- Operationg temperature : -5¡É ~ 55¡É
- Operationg Humidity : 90%RH Max
(none
condensing)
- Power supply
- AC : 110V or 220V/60Hz ¡¾10%, approx
3VA
- DC : 18V ~ 30V ¡¾10%, approx 3VA
- Power selection : AC 110V/220V Switch
in
the back plane
- Mounting : Wall or DIN rail
- PERFORMANCE
- Accuracy : ¡¾ 0.2%
- Temp'coefficient : ¡¾0.015¡É
- Response time : 0.5 Sec or less (0~90%)
- Insulation resistance : 100M¥Ø or more
with
DC 500V (Input/Output/Power)
- Dielectric strength : AC 1500V at 1 minute
(Input
to Output to Power)
|
- OUTPUT
- DC VOLTAGE : ¡¾ 12V Max
- Load Resistance
|
Output
|
Resistance
|
|
0 ~ 10mV
|
1K¥Ø or more
|
|
0 ~ 100mV
|
1K¥Ø or more
|
|
0 ~ 1V
|
1K¥Ø or more
|
|
0 ~ 5V
|
2K¥Ø or more
|
|
0 ~ 10V
|
4K¥Ø or more
|
|
-10V ~ 10V
|
4K¥Ø or more
|
- DC CURRENT : 0 ~ 20mA
- Load Rsistance
|
Output
|
Resistance
|
|
0 ~ 1mA
|
15K¥Ø or less
|
|
0 ~ 10mA
|
1.5K¥Ø or less
|
|
0 ~ 20mA
|
750¥Ø or less
|
|
1 ~ 5mA
|
3K¥Ø or less
|
|
4 ~ 20mA
|
750¥Ø or less
|
|